H05V2-K & H07V2-K
- REACH
- RoHS
- CE
- CPR Compliant
Application
Heat resistant cable designed for internal wiring in switch control, relay and instrumentation panels of power switchgear and for purposes such as internal connectors in rectifier equipment, motor starters and controllers.
Standard
BS/VDE EN 50525-2-31.
Technical Data
Voltage Rating: H05V2-K 0.5 to 1 mm² – 300 / 500V, H07V2-K 1.5 to 35 mm² – 450 / 750V
Temperature Range: -30°C to +90°C
Minimum Bending Radius :
Cable diameter ≤ 8 mm: 4 x outer diameter
Approx. diameter > 8 to 12 mm: 5 x outer diameter
Approx. diameter > 12 mm: 6 x outer diameter
Test Voltage: 2500V
Construction
Conductor Class 5 flexible plain / metal coated stranded according to EN 60228.
Insulation PVC (Polyvinyl Chloride) TI3 to BS EN 50363 – 3.
Properties
- PVC self-extinguishing and flame retardant according to EN 60332-1-2.
Cabel Design Parameters
Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required:
01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green/yellow, 07 – white, 08 – violet, 09 – brown, 10 – orange, 11 – pink, 12 – grey.
By adding the suffix (in place of ‘c’) for the conductor type required:
0 = Annealed Bare Copper (ABC), 1 = Annealed Tinned Copper (ATC).
Part Numbers | Nominal Cross Sectional Area (Sq. mm) | Nominal Thickness of Insulation (mm) | Mean Overall Diameter | Approx. Cable Weight (kg/km) |
||
Lower Limit (mm) | Upper Limit (mm) | |||||
H05V2-K | 02030101xx3c | 0.5 | 0.6 | 2.1 | 2.5 | 8.5 |
02030102xx3c | 0.75 | 0.6 | 2.2 | 2.7 | 11.5 | |
H07V2-K | 02030104xx3c | 1.5 | 0.7 | 2.8 | 3.4 | 20 |
02030105xx3c | 2.5 | 0.8 | 3.4 | 4.1 | 32 | |
02030106xx3c | 4 | 0.8 | 3.9 | 4.8 | 46 | |
02030107xx3c | 6 | 0.8 | 4.4 | 5.3 | 65 | |
02030108xx3c | 10 | 1.0 | 5.7 | 6.8 | 110 | |
02030109xx3c | 16 | 1.0 | 6.7 | 8.1 | 167 | |
02030110xx3c | 25 | 1.2 | 8.4 | 10.2 | 257 | |
02030111xx3c | 35 | 1.2 | 9.7 | 11.7 | 358 |
- For current ratings refer table no. 8-1 & 8-2.