Search results will appear here

JB-YSY

  • REACH
  • RoHS
  • CE
JB-YSY
JB-YSY-Cross

Application

These cables are used as measuring and control cables in food processing industries, packaging industries, tool machinery, plant installation and power stations. The steel braid ensures best possible protection against mechanical damage. The galvanized coating on the steel wire braiding not only helps protect against corrosion, but also notably improves the soldering properties.

Standard

Adapted to DIN/BS EN 50525-2-51

Technical Data

Nominal Voltage: Uo / U 300 / 500V up to 1.5 mm². Uo/U 450/750V for 2.5 mm² and above

Insulation Resistance: Min. 20 GΩ x cm

Temperature Range: Flexing -5°C to +70°C; Fixed installation -30°C to +70°C

Minimum Bending Radius: Flexing 20 x cable ø. Fixed installation 6 x cable ø

Test Voltage: 4000V

Breakdown Voltage: Min. 8000V

Cable Construction

Bare copper, fine wire conductors, to EN 60228 Cl. 5.
Core insulation of TI2, EN 50363-3.
Core identification : As per VDE 0293-302/HD 308 S2 (Refer appendix table No. 1-1)
Green/Yellow earth core in outer layer (3 cores and above).
Cores stranded in layers with optimal lay-length.
Special PVC inner jacket.
Galvanised steel wire screening.
Special PVC outer jacket.
Transparent Special PVC outer sheath (also available in grey)

Properties

PVC self-extinguishing and flame retardant according to EN 60332-1-2.

Cable Design Parameters

Please complete the part numbers for these cables by adding the suffix (in place of ‘z’) for the sheath colour required,
3 – grey (RAL 7001), 6 – transparent.

Part NumberNo. of Cores and Nominal
Cross Sectional Area (Sq. mm)
Approx. Cable
Diameter (mm)
Approx. Copper
Weight (kg/km)
Approx. Cable
Weight (kg/km)
03070101021z2 x 0.759.018120
03070102011z3G 0.759.427138
03070103011z4G 0.7510.236176
03070104011z5G 0.7510.944204
03070105011z7G 0.7511.762250
03070106011z12G 0.7514.4107398
03070107021z2 x 19.324129
03070108011z3G 19.936166
03070109011z4G 110.647196
03070110011z5G 111.559234
03070111011z7G 112.383290
03070112011z25G 119.5296857
03070113021z2 x 1.510.435171
03070114011z3G 1.510.952205
03070115011z4G 1.511.969252
03070116011z5G 1.513.187307
03070117011z7G 1.514.1122381
03070118011z12G 1.517.3208618
03070119011z18G 1.519.7313873
03070120011z25G 1.522.64341183
03070121011z32G 1.524.75561480
03070122021z2 x 2.511.958238
03070123011z3G 2.512.587285
03070124011z4G 2.513.8116371
03070125011z5G 2.515.0145442
03070126011z7G 2.516.3203558
03070127021z2 x 412.992304
03070128011z4G 415.0184477
03070129011z5G 416.4230574
03070130011z3G 615.2207492
03070131011z4G 616.6276638
03070132011z5G 618.1345770
03070133011z4G 1021.34701042
03070134011z5G 1023.35881270
03070135011z4G 1624.17831479
03070136011z5G 1626.69791858
03070137011z4G 2529.412182258
03070138011z5G 2532.615222831
03070139011z4G 3532.417152955
03070140011z5G 3536.021443711
03070141011z4G 5038.824614256

Note:

  • *JB = With green/yellow earth core
  • OB = Without green/yellow earth core
  • For current ratings to DIN VDE 0298-4 refer table no. 12-3 of Appendix.