Search results will appear here

EXVB

  • REACH
  • RoHS
  • CE
  • CPR Compliant
EXVB
EXVB-Cross

Application

EXVB is a power distribution cable suitable for low voltage applications in power plants, transformer stations, industrial plants, metropolitan networks and in other electric plants where heavier current and thermal loads are expected. This cable is mainly suitable for fixed installations in ground, canals, concrete and in areas free from heavy mechanical stress.

Standard

HD 603 Part 5/ Sect.A & IEC 60502-1

Technical Data

Nominal Voltage: Uo / U 0.6/1.0 kV

Temperature Range: -5°C to 90°C

Maximum Conductor Temperature: 12 x D

Cable Construction

Conductor: Plain Copper conductor RE,RM,SM (Class-1 & Class-2)

Insulation: Crosslinked polyethylene (XLPE)

Core colours:

3C: brown, black & grey

4C: blue, brown, black, grey

Inner sheath : Special Bedding Compound

Outer sheath: Special PVC outer sheath

Sheath Colour: Black

*Water proof variant of this cable, EXeVB is also available with special water blocking tape.

Properties

Self-extinguishing and flame retardant according to IEC 60332-1-2.

Cabel Design Parameters


Part
Number

No. of Cores and
Nominal Cross-Section Area
(Sq. mm)

Nominal
Insulation
Thickness (mm)

Nominal Bedding
Thickness (mm)

Nominal Outer
Sheath Thickness
(mm)

Approx. Overall
Diameter
(mm)

Approx. Cable
Weight (kg/km)
1127010100913 x 1.50.711.812.0209
1127010200913 x 1.50.711.812.0199
1127010300913 x 2.50.711.813.0257
1127010400913 x 2.50.711.812.0244
1127010500913 x 40.711.814.0326
1127010600913 x 40.711.813.0307
1127010700913 x 60.711.814.0385
1127010800913 x 100.711.816.0533
1127010900913 x 100.711.816.0531
1127011000914 x 1.50.711.813.0241
1127011100914 x 1.50.711.812.0229
1127011200914 x 2.50.711.814.0301
1127011300914 x 2.50.711.813.0285
1127011400914 x 40.711.814.0365
1127011500914 x 60.711.816.0492
1127011600914 x 60.711.815.0463
1127011700914 x 100.711.818.0679
1127011800914 x 100.711.817.0648
1127011900914 x 160.711.820.0855
1127012000914 x 250.911.823.01265
1127012100914 x 350.911.826.01653
1127012200914 x 50111.8729.02168
1127012300914 x 701.11.22.0334.03066
1127012400914 x 951.11.22.1738.04111
1127012500914 x 1201.21.22.342.05109
1127012600914 x 2401.71.62.8458.010193

Current Carrying Capacity


Nominal Cross Sectional Area
(Sq. mm)

Current Carrying Capacity (Amp.)

In Ground at 30°C

In Air at 40°C
1.52824
2.53533
44439
65550
107467
169485
95120125
120145155
150170190
185210235
240250290

*Construction Product Regulation (CPR) is a regulation issued by the European Union with the purpose of regulating the limits of fire resistance and dangerous substances in the materials used in construction. This regulation applies to all products intended to be incorporated, permanently, in construction. Above link provides the DOP (declaration of performance) for the CPR compliance for the product.)