H05Z-K & H07Z-K

  • REACH
  • RoHS
  • CE
  • CPR Compliant
H05Z-K & H07Z-K
H05Z-K & H07Z-K-Cross

Application

Halogen-free single-core wires are used for installation in dry environments for wiring up lighting fixtures and units where valuable assets are to be protected from further damage resulting from fire. These cables may be installed on, in and beneath plaster, as well as in closed installation ducts. The direct operating voltages is permitted up to 900 V against ground when they are used in rail-coaches. For the inner wiring of switch boards and distributors these are to be used with an alternating nominal voltage up to 1000V or a direct voltage up to 750V against ground.

Standard

BS EN 50525-3-41.

Technical Data

Nominal Voltage : H05Z-K Uo / U 300 / 500V, H07Z-K Uo / U 450 / 750V

Harmonised Designation: 0.5 mm² to 1 mm² – H05Z-K, 1.5 mm² to 240 mm² – H07Z-K

Temperature Range: -15°C to +90°C

Minimum Bending Radius :

Cable diameter ≤ 8 mm: 4 x outer diameter

Approx. diameter > 8 to 12 mm: 5 x outer diameter

Approx. diameter > 12 mm: 6 x outer diameter

Test Voltage: 2500V

Cable Construction

Conductor Class 5 flexible plain/metal coated stranded according to EN 60228.

Insulation Polyolefin cross linked EI5 to EN 50363-5.

Tests

Smoke density to acc. to EN 61034-2

Halogen free acc. to EN 50525-1, EN 60754-1.

Corrosivity acc. to EN 60754-2

Ozone resistant according to EN 60811-2-1.

Self-extinguishing and flame retardant according to EN 60332-1-2.

LSOH = Low Smoke Zero Halogen-Free.

Cabel Design Parameters

Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required:
01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green/yellow, 07 – white, 08 – violet, 09 – brown, 10 – orange, 11 – pink,
12 – grey.
By adding the suffix (in place of ‘c’) for the conductor type required:
0 = Annealed Bare Copper (ABC), 1= Annealed Tinned Copper (ATC).

Part NumbersNominal Cross
Sectional Area
(Sq. mm)
Nominal Thickness
of Insulation
(mm)
Mean Overall Diameter
Approx. Cable
Weight
(kg/km)
Lower Limit (mm)Upper Limit (mm)
H05Z-K02040101xx6c0.50.61.92.49
02040102xx6c0.80.62.12.612
02040103xx6c10.62.22.815
H07Z-K02040104xx6c1.50.72.83.521
02040105xx6c2.50.83.44.333
02040106xx6c40.83.94.947
02040107xx6c60.84.45.566
02040108xx6c101.05.77.1112
02040109xx6c161.06.78.4169
02040110xx6c251.28.410.6260
02040111xx6c351.29.712.1358
02040112xx6c501.411.514.4509
02040113xx6c701.413.216.61701
02040114xx6c951.615.118.8925
02040115xx6c1201.616.720.91168
02040116xx6c1501.818.623.31456
02040117xx6c1852.020.625.81773
02040118xx6c2402.223.529.42329
  • For current ratings refer table no. 9-1 & voltage drop refer table no. 9-2.

*Construction Product Regulation (CPR) is a regulation issued by the European Union with the purpose of regulating the limits of fire resistance and dangerous substances in the materials used in construction. This regulation applies to all products intended to be incorporated, permanently, in construction. Above link provides the DOP (declaration of performance) for the CPR compliance for the product.)