“B” | “C” | |
Standard Conformity | IS/IEC 60898-1 | |
No. of Pole | 1P, 1P+N, 2P, 3P, 3P+N, 4P* | |
Magnetic Release Setting | (3-5)In | (5-10)In |
Method of Mounting | Clip on Din rail (35×7.5mm) | |
Rated Operational Voltage | 240/415V | |
Rated Current | 6 to 63A* | |
Rated Frequency | 50Hz | |
Rated Short Circuit Capacity | 10kA | |
Max. Value of I2 t (Joule Integral) | 125000 | |
Rated Insulation Voltage | 660V | |
Rated Impulse with stands Voltage | 4kV | |
Material Group | III a | |
IP Category | IP20 | |
Ambient Temp. | -5º to 55ºC | |
Tightening Torque | 2.Nm | |
Dielectric Test Voltage | 2.5kV | |
Energy Limiting Class | 3 | |
Vibration | 3g | |
Installation Position | Vertical/Horizontal | |
Bi-connect Terminal | Both side | |
Line & Load Terminal Capacity | 25 mm2 | |
Resistance to Shock | 40mm free fall | |
Endurance Mechanical & Electrical Cycles | 8000 |
*CURRENT RATING
- 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A
- *1P = Single Pole
- *1P+N = Single Pole & Neutral
- *2P = Double Pole
- *3P = Three Pole
- *3P+N = Three Pole & Neutral
- *4P = Four Pole
Miniature Circuit Breakers have precisely formed molded case & cover of flame-retardant high strength thermo-plastic material having high melting point, low water absorption, high dielectric strength and temperature with stand. The Switching Mechanism is independent, manual and trip free, i.e, the breaker trips internally even if the operating knob is held in ON position.
The Contact Mechanism comprises of fixed & moving contacts specially designed for reliability, long life and anti-weld properties. The Arc Extinguishing Device comprises of 12 plates arc chute. The arc under the influence of the magnetic field and arc guide is moved into the arc chute where it is rapidly split and quenched. The tripping mechanism is thermal magnetic type.
THERMAL OPERATION
The thermal operation provides protection from moderate overload. During a current overload, a thermo-metallic element (bimetallic strip) deflects until it operates a latching mechanism allow the main contacts to open.
MAGNETIC OPERATION
In a magnetic operation, large overloads or short circuit current actuates a solenoid causing a plunger to strike the latching mechanism rapidly opening the main contacts.
Type B Characteristics curves
Type C Characteristics curves
Large & Dual Terminals
MCB Padlock
Energy Limiting Class 3
Effective Air Circulation
Fire Retardant
IP 20 Protection
ON/OFF Indication
BI-stable Din Clip
10kA Breaking Capacity
Low Power Consumption