Superex FR
- REACH
- RoHS
- CE
- CPR Compliant
India’s 1st REACH and RoHS Compliant Cable | Flame Retardant Cable.
Application
Suitable for wiring in all types of residential and commercial infrastructure, where fire and electrical safety is utmost important.
Technical Data
Approvals: IS 694 marked, FIA/TAC
Voltage Grade: Up to and including 1100V
Conductor: Thin strands of electrolytic copper are multi-drawn for uniformity of resistance, dimension and flexibility. The strands are twisted with high precision to impart circularity for the conductor
Insulation: Specially formulated flame retardant PVC insulation is used. The FR property retards the propagation of flame without compromising safety
Insulation Conformity: IS 5831, Type A/D FR 70°C
Colours: Red, yellow, blue, black, green, grey & white
Marking: The cables are printed with marking of ‘SUPEREX FR’
Packing: 90 mtr. coil is packed in protective cartons. Project packing of 180 mtr. also available.
Cabel Design Parameters
Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required:
01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – grey, 07 – white.
Part Number | Nominal Cross Sectional Area (sq. mm) | Nominal Insulation Thickness (mm) | Number / *Max. Dia. Of Strands | Approx. Overal Diameter (mm) | Max.DC Conductor Resistance at 20°C (Ω/km) | Current Rating (Amps) | |
Casing | Concealed | ||||||
01010102xx20 | 0.75** | 0.6 | 24/0.2 | 2.3 | 26.0 | 9 | 8 |
01010103xx20 | 1 | 0.7 | 14/0.3 | 2.7 | 18.1 | 14 | 13 |
01010104xx20 | 1.5 | 0.7 | 22/0.3 | 3.0 | 12.1 | 18 | 16 |
01010105xx20 | 2.5 | 0.8 | 36/0.3 | 3.7 | 7.41 | 24 | 20 |
01010106xx20 | 4** | 0.8 | 56/0.3 | 4.1 | 4.95 | 30 | 26 |
01010107xx20 | 6** | 0.8 | 84/0.3 | 4.6 | 3.30 | 38 | 33 |
- *Conductor as per IS 8130
- **Insulation Type D as per IS 5831
Properties
Test | Test Test Method | Values |
Limited Oxygen Index | IS 10810 P-58 | > 29% |
Limited Temp. Index | IS 10810 P-64 | >250 °C |
*Construction Product Regulation (CPR) is a regulation issued by the European Union with the purpose of regulating the limits of fire resistance and dangerous substances in the materials used in construction. This regulation applies to all products intended to be incorporated, permanently, in construction. Above link provides the DOP (declaration of performance) for the CPR compliance for the product.)